Danfoss VLT AutomationDrive FC 301 Operating Instructions Manual page 37

0.25-75 kw
Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Application Set-up Examples
6.1.6 Motor Thermistor
CAUTION
THERMISTOR INSULATION
Risk of equipment damage.
Use only thermistors with reinforced or double
insulation to meet PELV insulation
requirements.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.12 Motor Thermistor
MG33AP02
Operating Instructions
Parameters
Function
Setting
1-90 Motor
[2]
Thermal
Thermistor
Protection
trip
1-93 Thermistor
[1] Analog
Source
input 53
* = Default Value
Notes/comments:
If only a warning is desired,
parameter 1-90 Motor Thermal
Protection should be set to [1]
Thermistor warning.
D IN 37 is an option.
Danfoss A/S © Rev. 07/2014 All rights reserved.
6.1.7 SLC
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
20
COM
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Table 6.13 Using SLC to Set a Relay
Parameters
Function
Setting
4-30 Motor
[1] Warning
Feedback Loss
Function
4-31 Motor
100 RPM
Feedback Speed
Error
4-32 Motor
5 s
Feedback Loss
Timeout
7-00 Speed PID
[2] MCB 102
Feedback Source
17-11 Resolution
1024*
(PPR)
13-00 SL
[1] On
Controller Mode
13-01 Start Event [19] Warning
13-02 Stop Event
[44] Reset
key
13-10 Comparator
[21] Warning
Operand
no.
13-11 Comparator
[1] ≈*
Operator
13-12 Comparator
90
Value
13-51 SL
[22]
Controller Event
Comparator
0
13-52 SL
[32] Set
Controller Action
digital out A
low
5-40 Function
[80] SL
Relay
digital
output A
*=Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 is issued. The SLC monitors
Warning 90 and if Warning 90
becomes TRUE, Relay 1 is
triggered.
External equipment may then
indicate that service may be
required. If the feedback error
goes below the limit again
within 5 s, the frequency
converter continues and the
warning disappears. But Relay 1
is still triggered until [Reset] on
the LCP.
35
6
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents