8.7 Fuses and Circuit Breakers

Use recommended fuses and/or circuit breakers on the supply side as protection in case of component break-down inside
the frequency converter (first fault).
NOTICE
Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations.
Recommendations:
gG type fuses.
Moeller type circuit breakers. For other circuit breaker types, ensure that the energy into the frequency converter is
equal to or lower than the energy provided by Moeller types.
Use of recommended fuses and circuit breakers ensures that possible damage to the frequency converter is limited to
damages inside the unit. For further information, see Application Note Fuses and Circuit Breakers.
The fuses below are suitable for use on a circuit capable of delivering 100000 A
frequency converter voltage rating. With the proper fusing, the frequency converter Short-circuit Current Rating (SCCR) is
100000 A
.
rms
8.7.1 CE Compliance
200-240 V
Enclosure
Power [kW]
A1
0.25-1.5
A2
0.25-2.2
A3
3.0-3.7
A4
0.25-2.2
A5
0.25-3.7
B1
5.5-7.5
B2
11
B3
5.5
B4
7.5-15
C1
15-22
C2
30-37
C3
18.5-22
C4
30-37
Table 8.13 200-240 V, Enclosure Types A, B and C
MG33AP02
Operating Instructions
Recommended
Recommended
fuse size
maximum fuse
gG-10
gG-10 (0.25-1.5)
gG-16 (2.2)
gG-16 (3)
gG-20 (3.7)
gG-10 (0.25-1.5)
gG-16 (2.2)
gG-10 (0.25-1.5)
gG-16 (2.2-3)
gG-20 (3.7)
gG-25 (5.5)
gG-32 (7.5)
gG-50
gG-25
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
gG-63 (15)
gG-160 (15-18.5)
gG-80 (18.5)
aR-160 (22)
gG-100 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
gG-80 (18.5)
gG-150 (18.5)
aR-125 (22)
aR-160 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
Danfoss A/S © Rev. 07/2014 All rights reserved.
(symmetrical), depending on the
rms
Recommended circuit
breaker
Moeller
gG-25
PKZM0-16
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-63
PKZM4-50
gG-125
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
NZMB2-A250
8
Maximum trip level
[A]
16
25
25
25
25
63
100
50
100
160
250
150
250
65
8