Wiring To Control Terminals; Enabling Motor Operation (Terminal 27) - Danfoss VLT AutomationDrive FC 301 Operating Instructions Manual

0.25-75 kw
Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Electrical Installation
Terminal
Parameter
61
4
4
68 (+)
69 (-)
01, 02, 03
04, 05, 06
Table 4.3 Terminal Description Serial Communication
Additional terminal:
2 form C relay outputs. The location of the
outputs depends on the frequency converter
configuration.
Terminals located on built-in optional equipment.
See the manual provided with the equipment
option.

4.8.2 Wiring to Control Terminals

Control terminal connectors can be unplugged from the
frequency converter for ease of installation, as shown in
Illustration 4.7.
NOTICE
Keep control wires as short as possible and separate
from high power cables to minimise interference.
1.
Open the contact by inserting a small screwdriver
into the slot above the contact and push the
screwdriver slightly upwards.
18
Terminal description
Default
setting
Serial communication
-
Integrated RC-filter for
cable screen. ONLY for
connecting the screen
in the event of EMC
problems.
8-3*
RS-485 interface. A
control card switch is
8-3*
provided for
termination resistance.
Relays
[0] No
Form C relay output.
5-40 [0]
operation
For AC or DC voltage
5-40 [1]
[0] No
and resistive or
operation
inductive loads.
Danfoss A/S © Rev. 07/2014 All rights reserved.
Operating Instructions
Description
Illustration 4.9 Connecting Control Wires
2.
3.
4.
See chapter 8.5 Cable Specifications for control terminal
wiring sizes and chapter 6 Application Set-up Examples for
typical control wiring connections.
4.8.3 Enabling Motor Operation (Terminal
A jumper wire may be required between terminal 12 (or
13) and terminal 27 for the frequency converter to operate
when using factory default programming values.
NOTICE
The frequency converter cannot operate without a signal
on terminal 27, unless terminal 27 is re-programmed.
Insert the bared control wire into the contact.
Remove the screwdriver to fasten the control wire
into the contact.
Ensure that the contact is firmly established and
not loose. Loose control wiring can be the source
of equipment faults or less than optimal
operation.
27)
Digital input terminal 27 is designed to receive 24
V DC external interlock command.
When no interlock device is used, wire a jumper
between control terminal 12 (recommended) or
13 to terminal 27. This provides an internal 24 V
signal on terminal 27.
When the status line at the bottom of the LCP
reads AUTO REMOTE COAST, this indicates that the
unit is ready to operate but is missing an input
signal on terminal 27.
When factory installed optional equipment is
wired to terminal 27, do not remove that wiring.
MG33AP02

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents