ALARM 52, AMA low I
nom
The motor current is too low. Check the settings in
4-18 Current Limit.
ALARM 53, AMA motor too big
The motor is too big for the AMA to operate.
ALARM 54, AMA motor too small
The motor is too small for the AMA to operate.
ALARM 55, AMA parameter out of range
The parameter values of the motor are outside of the
acceptable range. AMA cannot run.
ALARM 56, AMA interrupted by user
The user has interrupted AMA.
ALARM 57, AMA internal fault
Try to restart AMA again. Repeated restarts can over heat
the motor.
ALARM 58, AMA Internal fault
Contact the Danfoss supplier.
WARNING 59, Current limit
The current is higher than the value in 4-18 Current Limit.
Ensure that motor data in parameters 1–20 to 1–25 are set
correctly. Increase the current limit if necessary. Ensure that
the system can operate safely at a higher limit.
WARNING 60, External interlock
A digital input signal is indicating a fault condition external
to the frequency converter. An external interlock has
commanded the frequency converter to trip. Clear the
external fault condition. To resume normal operation,
apply 24 V DC to the terminal programmed for external
interlock. Reset the frequency converter.
WARNING/ALARM 61, Feedback error
An error between calculated speed and speed
measurement from feedback device. The function Warning/
Alarm/Disabling setting is in 4-30 Motor Feedback Loss
Function. Accepted error setting in 4-31 Motor Feedback
Speed Error and the allowed time the error occur setting in
4-32 Motor Feedback Loss Timeout. During a commissioning
procedure the function may be effective.
WARNING 62, Output frequency at maximum limit
The output frequency has reached the value set in
4-19 Max Output Frequency. Check the application to
determine the cause. Possibly increase the output
frequency limit. Be sure the system can operate safely at a
higher output frequency. The warning clears when the
output drops below the maximum limit.
ALARM 63, Mechanical brake low
The actual motor current has not exceeded the release
brake current within the start delay time window.
ALARM 64, Voltage Limit
The load and speed combination demands a motor
voltage higher than the actual DC-link voltage.
WARNING/ALARM 65, Control card over temperature
The cut-out temperature of the control card is 80 °C.
MG33AP02
Operating Instructions
Troubleshooting
WARNING 66, Heat sink temperature low
The frequency converter is too cold to operate. This
warning is based on the temperature sensor in the IGBT
module.
Increase the ambient temperature of the unit. Also, a
trickle amount of current can be supplied to the frequency
converter whenever the motor is stopped by setting
2-00 DC Hold/Preheat Current at 5% and 1-80 Function at
Stop.
ALARM 67, Option module configuration has changed
One or more options have either been added or removed
since the last power-down. Check that the configuration
change is intentional and reset the unit.
ALARM 68, Safe Stop activated
STO has been activated. To resume normal operation,
apply 24 V DC to terminal 37, then send a reset signal (via
bus, digital I/O, or by pressing [Reset]).
ALARM 69, Power card temperature
The temperature sensor on the power card is either too
hot or too cold.
Troubleshooting
ALARM 70, Illegal FC configuration
The control card and power card are incompatible. To
check compatibility, contact the Danfoss supplier with the
type code of the unit from the nameplate and the part
numbers of the cards.
ALARM 71, PTC 1 safe stop
STO has been activated from the VLT PTC Thermistor Card
MCB 112 (motor too warm). Normal operation can be
resumed when the MCB 112 applies 24 V DC to terminal
37 again (when the motor temperature reaches an
acceptable level) and when the digital input from the MCB
112 is deactivated. When that happens, send a reset signal
must be sent (via bus or digital I/O, or press [Reset]).
ALARM 72, Dangerous failure
STO with trip lock. An unexpected combination of STO
commands has occurred:
Danfoss A/S © Rev. 07/2014 All rights reserved.
Check that the ambient operating temperature is
within the limits.
Check for clogged filters.
Check the fan operation.
Check the control card.
Check that the ambient operating temperature is
within limits.
Check for clogged filters.
Check fan operation.