Specifications

8.4 Ambient Conditions

Environment
Enclosure
Vibration test
Maximum THVD
Maximum relative humidity
Aggressive environment (IEC 60068-2-43) H
Ambient temperature
1)
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
EMC standards, Emission
EMC standards, Immunity
Energy efficiency class
2)
1) Refer to Special Conditions in the Design Guide, for:
Derating for high ambient temperature.
Derating for high altitude.
2) Determined according to EN50598-2 at:
Rated load
90% rated frequency
Switching frequency factory setting
Switching pattern factory setting

8.5 Cable Specifications

Cable lengths and cross-sections for control cables
Maximum motor cable length, screened
Maximum motor cable length, unscreened
Maximum cross-section to control terminals, flexible/rigid wire without cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross-section to control terminals
1) For power cables, see electrical tables in chapter 8.1 Electrical Data.

8.6 Control Input/Output and Control Data

Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
2)
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
2)
Maximum voltage on input
Pulse frequency range
(Duty cycle) Min. pulse width
Input resistance, R
i
MG33AP02
Operating Instructions
IP20/Chassis, IP21/Type 1, IP55/ Type 12, IP66/ Type 4X
5% - 93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
1)
1)
Danfoss A/S © Rev. 07/2014 All rights reserved.
Max. 50 °C (24-hour average maximum 45 °C)
1.5 mm
0.5 mm
0.25 mm
FC 301: 4 (5)
18, 19, 27
1.0 g
10%
class Kd
0 °C
- 10 °C
-25 to +65/70 °C
1000 m
EN 61800-3
EN 61800-3
IE2
8
150 m
300 m
2
/16 AWG
2
1 mm
/18 AWG
2
/20 AWG
2
/24 AWG
1)
1)
/FC 302: 4 (6)
1)
, 29
1)
, 32, 33,
PNP or NPN
0 - 24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
0-110 kHz
4.5 ms
approx. 4 kΩ
61
8