Application Set-up Examples
6.1.3 Start/Stop
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
32
D IN
D IN
33
D IN
37
+10
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.7 Start/Stop Command with Safe Stop Option
Speed
Start (18)
Illustration 6.2 Start/Stop Command with Safe Stop
MG33AP02
Operating Instructions
Parameters
Function
Setting
5-10 Terminal 18
[8] Start*
Digital Input
5-12 Terminal 27
[0] No
Digital Input
operation
5-19 Terminal 37
[1] Safe Stop
Safe Stop
Alarm
* = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.
D IN 37 is an option.
Danfoss A/S © Rev. 07/2014 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
32
D IN
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.8 Pulse Start/Stop
Speed
Latched Start (18)
Stop Inverse (27)
Illustration 6.3 Latched Start/Stop Inverse
Parameters
Function
Setting
5-10 Terminal 18
[9] Latched
Digital Input
Start
5-12 Terminal 27
[6] Stop
Digital Input
Inverse
* = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.
D IN 37 is an option.