Application Error - Delta AHCPU560-EN2 Series Operation Manual

Ethernet/ip
Table of Contents

Advertisement

Category
Error Code
16#12010302
16#12010315

6.2.3 Application Error

Category
Error Code
16#00010203
EtherNet/
16#30020000
IP Error
16#00010319
Description
Network Bandwidth NOT
Available for Data
Invalid Segment in
Connection Path
Description
1. Check the network connection status.
I/O Connection Timeout
2. Check if the module is working fine.
3. Increase the RPI value.
The Device Level Ring
(DLR) detects lost
Check the network connection status in the Ring topology.
connection.
1. Check the module number and the product setup file to
Secondary Resources
Unavailable
2. Reduce the number of the connections.
Ch a pt er 6 T r o u bl es h oo t in g
How to fix them
1. Check the I/O connection limit between the scanner
and the adapter.
2. Increase the RPI value or reduce the number of the
connections.
Check the module number and the product setup file to
see if they are matched.
How to fix them
see if they are matched.