Delta AHCPU560-EN2 Series Operation Manual page 49

Ethernet/ip
Table of Contents

Advertisement

Name
Requested Packet Interval (RPI)
Multicast
Timeout
Trigger Mode
Operation Steps:
1. Create a data mapping table (※):
 Click to select the Scanner Ethernet COM port that you'd like to perform the data mapping and then
right-click to see the options. Click Data Exchange to open the Data Mapping Table.
After the selection is made, the system will create a Data Mapping Tab, shown as Network_0.
RPI setup: via the I/O connection to connect to EtherNet/IP to
exchange data at regular time intervals, unit: ms
Communication mode setup: Multicast or Point-to-Point
Timeout setup; set up the timeout time according to the RPI or the
multiple of RPI (RPI*X).
Trigger Mode: Cyclic, Change of State, and Application
Cyclic: renew data cyclically
Change of State: renew data once there is any change
Application: renew data according to the product setup
Data Mapping Tab
Network_0 Data Mapping Table
C ha pt er 4 E I P B u il der
Definition
4_
4 - 2 5