E t h e r N e t / I P O p e r a t i o n M a n u a l
Category
_6
Data
Exchange
Setup Error
6 - 4
Error Code
Description
The output connection
16#11010123
type parameters in the
EDS file are mismatched.
The input connection type
16#11010124
parameters in the EDS file
are mismatched.
The output redundant
ownership parameters in
16#11010125
the EDS file are
mismatched.
The configuration size
16#11010126
parameters in the EDS file
are mismatched.
The configuration path
16#11010129
parameters in the EDS file
are mismatched.
The EDS file does not
16#11010132
support the Null forward
open.
I/O Connections
16#12010100
Duplicated
16#12010106
Ownership Conflict
Target for Connection not
16#12010110
Configured
Adapter RPI Not
16#12010111
Supported
16#12010113
Out of Connections
Non-Listen Only Not
16#12010119
Opened
Invalid Originator to
16#12010127
Target Size
Invalid Target to
16#12010128
Originator Size
Consumed Tag does not
16#1201012D
exist.
Produced Tag does not
16#1201012E
exist.
Unconnected Request
16#12010204
Timeout
How to fix them
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
1. Check if the system has created the I/O connections.
2. Change the connection type to Listen Only.
1. Check the scanner owner.
2. Reconfigure the invalid scanner.
3. Change the connection to multicast.
1. Check the I/O connection status.
2. Activate the I/O connections again.
Check the RPI for the adapter.
1. Check if the connection exceeds the limit.
2. Reduce the number of the product connection.
1. Check if the system has created the I/O connections.
2. Check the scanner I/O connection status.
Check the module number and the product setup file to
see if they are matched.
Check the output size in the connection parameters.
Check if the parameters in the consumed tag are
correctly set.
Check if the parameters in the produced tag are
correctly set.
No response from the adapter; check if the power and
the network connection of the adapter are working
properly.