ID
138
139
140
141
142
143
144
145
146
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB
Icons
Message
Totalizer 1 below warning
limit
Totalizer 1 below alarm
limit
Totalizer 2 above alarm
limit
Totalizer 2 above warning
limit
Totalizer 2 below warning
limit
Totalizer 2 below alarm
limit
Totalizer 3 above alarm
limit
Totalizer 3 above warning
limit
Totalizer 3 below warning
limit
Diagnostics and troubleshooting
10.2 Fault codes and corrective actions
Cause/Action
Check process conditions. Adjust the parameter value
'Lower warning limit' to normal process conditions.
Check process conditions. Adjust the parameter value
'Lower alarm limit' to normal process conditions.
Check process conditions. Adjust the parameter value 'Up‐
per alarm limit' to normal process conditions.
Check process conditions. Adjust the parameter value 'Up‐
per warning limit' to normal process conditions.
Check process conditions. Adjust the parameter value
'Lower warning limit' to normal process conditions.
Check process conditions. Adjust the parameter value
'Lower alarm limit' to normal process conditions.
Check process conditions. Adjust the parameter value 'Up‐
per alarm limit' to normal process conditions.
Check process conditions. Adjust the parameter value 'Up‐
per warning limit' to normal process conditions.
Check process conditions. Adjust the parameter value
'Lower warning limit' to normal process conditions.
181