SECTION 3
EDRP-IOM-2019-0212
When in Automatic Control, the temperature controller will modulate the
burner to a firing rate necessary to achieve the setpoint. To enter Manual
Control, tap the "Automatic Control" button, and it will change to "Manual
Control. " Enter a "Manual Firing Rate" in the box, and press OK to confirm.
When finished with maintenance, return to this screen and place the boiler
back into Automatic Control.
The Anti-Cycle Timer, if used, will prevent the burner from firing for a minimum
amount of time between cycles
` BOILER HISTORY
Various data points of operational history are summarized on this screen.
` ALARM HISTORY
This screen provides a chronological list of alarms. Pressing the "View Alarm
Info" button will expand a selected alarm for additional information and
troubleshooting tips.
` MAINTENANCE LOG
Access a history of preventative maintenance and repairs. Tapping "View Entry"
will expand detail on a previous record. Add a record of service by tapping "New
Entry" and completing the record.
` ISOLATION VALVE
This screen will only be accessible if Isolation Valve is selected. See Auxiliary
Configuration in Admin.
The isolation valve can be placed in manual control or automatic. When using
manual, ensure all boilers are not placed in manual close while the system pumps
are in operation. In automatic control, a Close Delay Timer can be set to keep the
boiler's isolation valve open for the prescribed time when a boiler no longer has a
call for heat. The Delta T Close Delay feature will hold the boiler isolation valve open
until residual heat is removed from the heat exchanger and the Delta T drops to the
selected value. When enabled, the isolation valve will not close until both conditions
are satisfied. One valve will always remain open when lead/lag is used.
` PRIMARY PUMP
This screen will only be accessible if Use Pump Control and Boiler Pump is selected.
See Auxiliary Configuration in Admin.
The purpose of this screen is to enable and disable a dedicated boiler pump
(primary pump) for Primary / Secondary piping arrangements only.
The pump can be placed in automatic control or manual. In automatic control,
the Stop Delay Timer will continue operating the pump for the prescribed time
after the call for heat ends. The Delta T Stop Delay will continue operating the
pump until residual heat is removed from the heat exchanger and the Delta T
drops to the selected value. When enabled, the pump will continue operation
until both conditions are satisfied.
Questions? Please Contact Your Local Manufacturer's Representative
OPERATION
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes
and regulations.
Non-Fulton product information
is for reference purposes only. No
Fulton document should substitute
for full review of documentation
available from the component
manufacturer.
3-15