FULTON Endura+ Series Installation And Operation Manual page 37

Condensing hydronic boilers
Table of Contents

Advertisement

SECTION 2
EDRP-IOM-2019-0212
FIGURE 20 - SIDEWALL PENETRATION DETAIL
TYPICAL SIDE WALL PENETRATIONS
( SUGGESTED INSTALLATION CONFIGURATIONS )
NOTES:
1) HORIZONTAL SECTIONS MUST ADHERE TO A MINIMUM
1/4 INCH PER FOOT (1 MM PER 48 MM) RISE TO RUN RATIO
2) MAINTAIN A MINIMUM 9 INCH (229 MM) AIR SPACE
CLEARANCE TO COMBUSTABLES, WIRE, AND INSULATION
3) INSTALL SUPPORT STRAPS AT 5 FT (152 CM) HORIZONTAL
INTERVALS AND AT ELBOWS
CAUTION:
SEPARATE AIR INTAKE AND EXHAUST TERMINATIONS AS FAR AS
POSSIBLE TO PREVENT FLUE GAS RECIRCULATION (FGR) DURING
DIFFERENT WIND CONDITIONS.
SCH40 PVC PIPE (TYPICAL)
REFERENCE TABLE 1 FOR MIN CAI DIAMETER
AIR INTAKE ADAPTER
(STYLE & LOCATION VARIES)
ENDURA+
HYDRONIC
BOILER
( SIDE VIEW )
LEVEL HOUSEKEEPING PAD
MIN 4 INCH (102 CM) HEIGHT
Questions? Please Contact Your Local Manufacturer's Representative
UL-1738 APPROVED
EXHAUST VENT MATERIAL
FLEXIBILE RUBBER
PIPE COUPLING
WALL TERMINATIONS DETAIL VIEW
EXHAUST STACK IS DOWNWIND
OF AIR INTAKE OPENING
COMBUSTION
AIR INLET 90° ELBOW
1/2 INCH x 1/2 INCH
(13 MM x 13 MM)
MESH SCREEN
MINIMUM RISE TO RUN RATIO:
1/4" PER FOOT (1 MM PER 48 MM)
UP TOWARDS TERMINATION
MINIMUM RISE TO RUN RATIO:
1/4" PER FOOT (1 MM PER 48 MM)
DOWN TOWARDS TERMINATION
COMBUSTION AIR INTAKE (CAI)
DIRECTION OF FLOW
FLUE GAS EXHAUST
DIRECTION OF FLOW
IN LINE STACK DRAIN
(RECCOMENDED FOR HIGH CONDENSATE
PRODUCTION RATE APPLICATIONS)
APPLIANCE ADAPTER
CONSULT FLUE MFG FOR SELECTION
REFERENCE TABLE 1 FOR FLUE GAS STACK DIAMETER
FLEXIBLE HOSE
CONDENSATE TRAP (STYLE VARIES)
INSTALLATION
FLUE GAS EXHAUST TERMINATION
MINIMUM 4 FT (122 CM) ABOVE THE
COMBUSTION AIR INLET TERMINATION
MINIMUM 10 FT (305 CM)
HORIZONTAL AWAY FROM THE
COMBUSTION AIR INLET TERMINATION
DO NOT PLACE
INSULATION IN
REQUIRED AIR SPACE
FLUE GAS EXHAUST TERMINATION
MINIMUM 10 FT (305 CM) HORIZONTAL
COMBUSTION AIR INLET TERMINATION
COMBUSTION
AIR INLET 90° ELBOW
1/2 INCH x 1/2 INCH
(13 MM x 13 MM)
MESH SCREEN
AND 4 FT (122 CM) ABOVE THE
OPENING TO BE MIN 1 FT (30 CM)
ABOVE NORMALLY EXPECTED
SNOW ACCUMULATION LEVEL
2-31