FULTON Endura+ Series Installation And Operation Manual page 24

Condensing hydronic boilers
Table of Contents

Advertisement

INSTALLATION
Figure Notes:
1. Header must be level or slightly pitched toward the
drain.
2. Header material must be CPVC, high-temperature
silicone tubing, galvanized steel, or stainless steel.
3. Header should be taken to the lowest point
possible and maintain a minimum 2-inch (51 mm)
drop from the boiler condensate drain outlet.
4. The condensate drain trap outlet must be below
the condensate outlet of the boiler.
5. For multiple boiler installation, maintain minimum
pipe size of one inch (25.4 mm) for the header
piping.
6. The maximum capacity to attach per multiple
boiler condensate drain trap is 12 MMBH total.
2-18
FIGURE 12 - CONDENSATE DRAIN PIPING FOR MULTIPLE ENDURA+ BOILERS
EDRP-IOM-2019-0212
HOUSEKEEPING PAD
MINIMUM 4-INCH (102 MM)
FLEXIBLE, DRAIN HOSE
(SUPPLIED, REQUIRED)
Note: A ¼" fresh water
makeup line is required.
HEADER MUST BE AT
FLOOR (NOT PAD) HEIGHT
¼" TAPPING PROVIDED
FOR FRESH WATER
CONNECTION
SIDE VIEW
BACK VIEW
SECTION 2
≥2"
© Fulton Group N.A., Inc. 2019