FULTON Endura+ Series Installation And Operation Manual page 55

Condensing hydronic boilers
Table of Contents

Advertisement

SECTION 3
EDRP-IOM-2019-0212
Questions? Please Contact Your Local Manufacturer's Representative
1) Confirm position of the fuel selection switch where
applicable.
2) Enter the password and parameter "400" will flash.
3) Press the enter (i/reset) button 2 times.
a. "P1" will flash and the curve point will be displayed.
 OTEE:
P0 is the ignition position. Verify proper combustion
at the ignition position.
4) With "P1" flashing the fuel or air actuator may be
individually selected for combustion adjustments.
a. For the fuel actuator keep the "F" button depressed
and press the "-" or "+" button to adjust the fuel
actuator.
i. Any changes are automatically saved.
ii. Release the "F" button.
b. For the air actuator keep the "A" button depressed and
the press the "-" or +" button to adjust the air actuator.
i. Any changes are automatically saved.
ii. Release the "A" button.
c. With "P1" flashing use the "+" for the next curve point
and the "-" for going back to the previous curve point.
d. Repeat steps "a. " and "b. " above if changes are required
at any other curve point.
OPERATION