Mounting External Housing - Vega VEGADIF 65 Operating Instructions Manual

4 ... 20 ma differential pressure transmitter with metallic measuring diaphragm
Table of Contents

Advertisement

When using chemi-
cal seal systems in all
products
VEGADIF 65 • 4 ... 20 mA
1. Mount chemical seal with capillaries on top or laterally on the
pipeline
2. In vacuum applications: Mount VEGADIF 65 below the measure-
ment loop
3. The ambient temperature should be the same for both capillaries
2
+
Fig. 32: Measurement setup, differential pressure measurement in gases,
vapours and liquids
1
Chemical seal with bolting
2
Capillaries
3
E.g. filter
4
VEGADIF 65
4.8

Mounting external housing

1. Mark the holes according to the following drilling template
2. Depending on the mounting surface, fasten the wall mounting
plate with 4 screws
Fig. 33: Drilling template - wall mounting plate
1
2
3
90 mm (3.54")
70 mm (2.76")
3 mm
(0.12")
4 Mounting
4
8 mm
(0.32")
31