Reset
VEGADIF 65 • 4 ... 20 mA
6 Adjustment with the display and adjustment module PLICSCOM
Damping
Linearization curve
Leak flow volume suppression
Sensor-TAG
Displayed value
Display unit
Scaling
Current output
Unit of measurement
Language
The following safety-relevant data are not uploaded or downloaded:
HART mode
PIN
Copy sensor data
Copy sensor data?
Basic adjustment
The reset "Basic adjustment" resets the values of the following menu
items to the reset values (see chart):
Menu section
Basic settings
Display
Diagnostics
Service
The values of the following menu items are not reset with "Reset:
Menu item
Zero/Min. adjustment
Span/Max. adjustment
Density
Density unit
Damping
Linearization
Sensor-TAG
Displayed value
Display unit
Scaling
Decimal point indication
Totalizer
Part sum counter
Current output - charac-
teristics
Current output - failure
mode
Current output - min.
current
Current output - max.
current
Reset value
Measuring range begin
Measuring range end
1 kg/l
kg/l
1 s
Linear
Sensor
Differential pressure
Mass/kg
0.00 to 100.0
8888.8
0.0000 10
gal
00
0.0000 10
gal
00
4 ... 20 mA
< 3.6 mA
3.8 mA
20.5 mA
49