7 Setup
Measurement setup for
closed vessels
Prepare the adjustment
58
III
Fig. 47: Preferred measurement setup for closed vessels
I
VEGADIF 65
II
3-fold valve block
III Separator
1, 5 Drain valves
2, 4 Inlet valves
6, 7 Vent valves on VEGADIF 65
A, B Blocking valves
Proceed as follows:
1. Fill the vessel to just above the lower tap
2. Fill measuring system with medium
Close valve 3: Separate plus and minus side
Open valve A and B: Open block valves
3. Vent plus side (probably empty minus side)
Open valve 2 and 4: Discharge medium on the plus side
Briefly open valve 6 and 7, then close again: Fill the plus side
completely with the medium and remove air.
4. Set measurement loop to operation
Now:
Valve 3, 6 and 7 are closed
Valves 2, 4, A and B are open
Then carry out adjustment, see below.
B
+
A
6
7
I
+
II
3
2
1
III
4
5
VEGADIF 65 • 4 ... 20 mA