4.5 Danfoss FC Control Profile

4.5.1 Control Word According to FC Profile
(CTW)
To select Danfoss FC protocol in the control word, set
parameter 8-10 Control Word Profile to [0] Frequency
converter profile. Use the control word to send commands
from a master (PLC or PC) to a slave (frequency converter).
Bit
Bit value = 0
00
Reference value
01
Reference value
02
DC brake
03
Coasting
04
Quick stop
05
Hold output frequency
06
Ramp stop
07
No function
08
No function
09
Ramp 1
10
Data invalid
11
No function
12
No function
13
Parameter set-up
14
Parameter set-up
15
No function
Table 4.8 Bit Values for FC Control Word
Explanation of the control bits
Bits 00/01 reference value
Use bits 00 and 01 to select between the 4 reference
values, which are pre-programmed in parameter 3-10 Preset
Reference according to Table 4.9.
NOTICE
In parameter 8-56 Preset Reference Select, a selection is
made to define how bit 00/01 gates with the
corresponding function on the digital inputs.
MG07F102
Programming Guide
Bit value = 1
External selection lsb
External selection msb
Ramp
No coasting
Ramp
Use ramp
Start
Reset
Jog
Ramp 2
Data valid
Relay 01 active
No function
Selection lsb
Selection msb
Reverse
Danfoss A/S © 05/2016 All rights reserved.
Bit 01
Bit 00
Programmed
reference value
0
0
1
0
1
2
1
0
3
1
1
4
Table 4.9 Programmed Reference Values for Bits
Bit 02, DC brake
Bit 02 = 0 leads to DC braking and stop. Braking current
and duration are set in parameter 2-01 DC Brake Current
and parameter 2-02 DC Braking Time.
Bit 02 = 1 leads to ramping.
Bit 03, coasting
Bit 03 = 0 causes the frequency converter immediately to
coast the motor to a standstill.
Bit 03 = 1 enables the frequency converter to start the
motor if the other starting conditions have been fulfilled.
NOTICE
In parameter 8-50 Coasting Select, a selection is made to
define how bit 03 gates with the corresponding function
on a digital input.
Bit 04, quick stop
Bit 04 = 0 quick stops the frequency converter and ramps
the motor speed down to stop via parameter 3-81 Quick
Stop Ramp Time.
Bit 04 = 1 makes the frequency converter ramp the motor
speed down to stop via parameter 3-42 Ramp 1 Ramp
Down Time or parameter 3-52 Ramp 2 Ramp Down Time.
Bit 05, hold output frequency
Bit 05 = 0 freezes the present output frequency (in Hz).
The frozen output frequency can only be changed with the
digital inputs (parameter 5-10 Terminal 18 Digital Input to
parameter 5-15 Terminal 33 Digital Input) programmed to
[21] Speed up and [22] Speed down.
Bit 05 = 1 uses ramp.