UMI-B1 UL Series Inverter
Function
Name
code
Output
P09.09
upper limit
of PID
Output
P09.10
lower limit
of PID
Feedback
offline
P09.11
detection
value
Feedback
offline
P09.12
detection
time
PID
P09.13
adjustment
selection
Detailed instruction of parameters
Reference
value
Output frequency
Setting range: 0.0–100.0%
These parameters are used to set the upper
and lower limit of the PID adjustor output.
100.0 % corresponds to Max. Frequency or
the Max. Voltage of ( P04.31)
Setting range of P09.09: P09.10–100.0%
Setting range of P09.10: -100.0%–P09.09
Set the PID feedback offline detection value,
when the detection value is smaller than or
equal to the feedback offline detection value,
and the lasting time exceeds the set value in
P09.12, the inverter will report "PID feedback
offline fault" and the keypad will display PIDE.
Output frequency
P09.11
Setting range of P09.11: 0.0–100.0%
Setting range of P09.12: 0.0–3600.0s
0x00–0x11
LED ones:
0: Keep on integral adjustment when the
frequency achieves the upper and low limit;
the integration shows the change between
the reference and the feedback unless it
reaches the internal integral limit. When the
Feedback value
Bias limit
t1<t2, so the inverter
continues to work
t2=P09.12
PIDE
t2
t1
Fault output PIDE
In running
81
Function parameters
Default
value
T
T
100.0%
0.0%
0.0%
1.0s
T
0x0001
Modify