Unitronics UMI-B1 UL Series Operation Manual page 80

Table of Contents

Advertisement

UMI-B1 UL Series Inverter
Function
Name
code
Current
adjustment
P08.51
coefficient
on the
input side
P09 Group
PID control
PID
P09.00
reference
source
Detailed instruction of parameters
The inverter monitors the state of the motor
continuously even during the magnetic flux
period. So the magnetic flux can be used in
the motor stop, as well as to change the
rotation speed of the motor. Its other
advantages are:
Brake immediately after the stop command. It
does not need to wait the magnetic flux
weaken.
The cooling is better. The current of the stator
other than the rotor increases during
magnetic flux braking, while the cooling of the
stator is more effective than the rotor.
This function code is used to adjust the
displayed current of the AC input side.
Setting range: 0.00–1.00
When the frequency command selection
(P00.06, P00. 07) is 7 or the voltage setting
channel selection (P04.27) is 6, the running
mode of the inverter is procedure PID
controlled.
The parameter determines the target given
channel during the PID procures.
0: Keypad digital given (P09.01)
1: Analog channel AI1 given
2: Analog channel AI2 given
3: Analog channel AI3 set
4: High speed pulse HDI set
5: Multi-step speed set
6: MODBUS communication set
7–9:Reserved
The setting target of procedure PID is a
relative one, 100% of the setting equals to
100% of the response of the controlled
system.
78
Function parameters
Default
Modify
value
0.56
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents