Common communication fault
Common communication faults: no response to the communication or the inverter
returns abnormal fault.
The possible reason for no response to the communication:
A wrong serial interface is selected, for example, the converter is COM1, but COM2 is
selected during the communication.
The baud rate, digital bit, end bit and check bit are not the same with the inverter + and -
of RS485 are connected in reverse.
The 485 wire cap on the terminal board of the inverter is not plug in. the wire cap in
behind the terminal arrangement.