UMI-B1 UL Series Inverter
Function
instruction
SW 1 of the
inverter
SW 1 of the
inverter
Fault code of the
inverter
Identifying code
of the inverter
Setting
frequency
Bus voltage
Output voltage
Output current
Operation speed
Output power
Output torque
PID setting
Address
Data meaning instruction
definition
motor)
AO output setting 1
200DH
(-1000–1000, 1000 corresponds to
100.0%)
AO output setting 2
200EH
(-1000–1000, 1000 corresponds to
100.0%)
0001H: forward running
0002H: reverse running
0003H: stop
2100H
0004H: fault
0005H: POFF state
0006H: pre-exciting state
Bit0: =0: bus voltage is not
established =1: bus voltage is
established
Bit1–2: =00: motor 1
Bit3: =0: asynchronous motor
2101H
=1: synchronous motor
Bit4: =0: pre-alarm without overload
=1: overload pre-alarm
Bit5–Bit6: =00: keypad control
2102H
See the fault type instruction
2103H
UMI-B1 UL-----0x0106
3001H
3002H
Compatible with UMI series,
3003H
CHF100A and CHV100
3004H
Compatible with UMI series,
3005H
CHF100A and CHV100
3006H
3007H
3008H
=01: motor 2
=10: motor 3
=11: motor 4
=01: terminal control
=10: communication control
122
Communication protocol
R/W
characteristics
W
W
R
R
R
R
R
R
R
R
R
R
R
R