UMI-B1 UL Series Inverter
Function
instruction
Communication
control
command
The address of
communication
setting
Set P00.01 to 2 and P00.06 to 8.
The command sent to the inverter:
Continuous
Inverter
writing
address
command
If the response message is as below:
Example 2: set the ACC time of 01H inverter as 10s and the DEC time as 20s
ACC time
P00.11
1
DEC time
P00.12
1
The corresponding address of P00.11 is 000B, the ACC time of 10s corresponds to
0064H, and the DEC time of 20s corresponds to 00C8H.
The command sent to the inverter:
Address
Data meaning instruction
definition
0001H: forward running
0002H: reverse running
0003H: forward jogging
0004H: reverse jogging
2000H
0005H: stop
0006H: coast to stop (emergency
stop)
0007H: fault reset
0008H: jogging stop
Communication setting frequency
2001H
(0–Fmax (unit: 0.01Hz))
PID given, range (0–1000, 1000
2002H
corresponds to100.0%)
Parameters
Data
address
number
Continuous
Inverter
Parameters
writing
address
command
ACC time means the time needed if the
inverter speeds up from 0Hz to the Max. One
(P00.03).
DEC time means the time needed if the
inverter speeds down from the Max. Output
frequency to 0Hz (P00.03).
UMI-B1 UL series inverters define four groups
of ACC/DEC time which can be selected by
P05. The factory default ACC/DEC time of the
inverter is the first group.
Setting range of P00.11 and P00.12:
0.0–3600.0s
Byte
Forward
number
running
Data
address
number
129
Communication protocol
R/W
characteristics
W/R
W/R
10Hz
CRC check
CRC check
Depen
d on
model
Depen
d on
model