UMI-B1 UL Series Inverter
Function
code
P10.00
P10.01
Note: P29 group is the factory parameter which cannot be read or changed. Some
parameters cannot be changed when the inverter is in the running state and some
parameters cannot be changed in any state. The setting range, unit and relative
instructions should be paid attention to when modifying the function code parameters.
Besides, EEPROM is stocked frequently, which may shorten the usage time of
EEPROM. For users, some functions are not necessary to be stocked on the
communication mode. The needs can be met on by changing the value in RAM.
Changing the high bit of the function code from 0 to 1 can also realize the function. For
example, the function code P00.07 is not stocked into EEPROM. Only by changing the
value in RAM can set the address to 8007H. This address can only be used in writing
RAM other than reading. If it is used to read, it is an invalid address.
7.3.5.2 The address instruction of other function in Modbus
The master can operate on the parameters of the inverter as well as control the inverter,
such as running or stopping and monitoring the working state of the inverter.
Below is the parameter list of other functions
Function
instruction
Communication
control
command
The address of
the
communication
setting value
Name
Description
0: Stop after running once
Simple
1: Run at the final value after running once
PLC
2: Cycle running
Simple
0: Power loss without memory
PLC
1: Power loss with memory
memory
Address
Data meaning instruction
definition
0001H: forward running
0002H: reverse running
0003H: forward jogging
0004H: reverse jogging
2000H
0005H: stop
0006H: coast to stop (emergency
stop)
0007H: fault reset
0008H: jogging stop
Communication setting frequency
2001H
(0–Fmax(unit: 0.01Hz))
PID reference, range (0–1000, 1000
2002H
corresponds to 100.0% )
PID feedback, range (0–1000, 1000
2003H
corresponds to 100.0% )
Setting
range
0–2
0–1
120
Communication protocol
Default
Modify Serial
No.
value
0
354.
0
355.
R/W
characteristics
W
W
W