UMI-B1 UL Series Inverter
3.2.2 Terminals figure of main circuit
Terminal
Terminal name
L
Power input of the main
N
U
V
The inverter output
W
PB, (+)
Braking resistor terminal
PE
Grounding terminal
Terminal
Terminal name
Power input of the main
R, S, T
U, V, W
The inverter output
PB, (+)
Braking resistor terminal
PE
Grounding terminal
Note:
Do not use asymmetrically motor cables. If there is a symmetrically grounding
conductor in the motor cable in addition to the conductive shield, connect the
grounding conductor to the grounding terminal at the inverter and motor ends.
Route the motor cable, input power cable and control cables separately.
When selecting C3 input filters, connect the filters in parallel at the input side of the
inverter.
Figure 3-4 1PH terminals of main circuit
1-phase AC input terminals which are generally
circuit
connected with the power supply.
3-phase AC output terminals which are generally
connected with the motor.
PB and (+) are connected to the external
resistor.
Each machine should be grounded.
Figure 3-5 3PH terminals of main circuit
3-phase AC input terminals which are generally
circuit
connected with the power supply.
3-phase AC output terminals which are generally
connected with the motor.
PB and (+) are connected to the external
resistor.
Each machine should be grounded.
15
Installation guide