Overview - Omron SYSMAC CS Series Operation Manual

Profibus master units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Overview

7-1

Overview

Troubleshooting on the
Master Unit
Troubleshooting the
Configuration Software
Troubleshooting the
network
202
The CS1/CJ1W-PRM21 PROFIBUS Master Unit and the Configuration soft-
ware package provides extensive means for troubleshooting, which can be
used to quickly determine errors in the Unit, in the configuration, in the net-
work, and/or in remote slave devices, allocated to the Unit.
For troubleshooting purposes, the following error indicators can be used:
• LED indicators on the front of the Unit
Three red error LED indicators and four status LED indicators show Unit
and network status and errors.
• CIO Words
Unit Status (CIO Word n + 4) containing status and error flags of the Unit,
and Master Status 2 (CIO Word n+6) containing error information about
the PROFIBUS network and the PROFIBUS functions of the Unit.
• The Error Log collects error codes for various error events. Serious errors
are stored in non-volatile memory and can be retrieved, even after a Unit
power down.
• FINS command provide defined response codes, which can indicate spe-
cific errors.
Note n = CIO 1500 + (25 x unit number).
This section provides a number of procedures for troubleshooting, based on
the error indicators listed above.
The Configuration software, i.e. CX-Profibus, the PROFIBUS Master DTM
and the Generic Slave DTM provide several mechanisms for error detection
and correction:
• Errors occurring in CX-Profibus are displayed in pop-up message win-
dows and/or the error log window. The contents of the error log window
can be copied to the clipboard to allow analysis afterwards.
• CX-Profibus provides a FDT communication log window, which can be
copied to the clipboard. Analysis of this communication may provide addi-
tional information in case errors occur.
The PROFIBUS Master DTM and the Generic Slave DTM diagnostics infor-
mation windows, which can display:
• Indications of errors in the PROFIBUS interface of the Unit
• Indications of errors in the communication between the PROFIBUS Mas-
ter Unit and remote slave devices.
• Indications of errors in the remote slave devices, allocated to the PROFI-
BUS Master Unit.
The CX-Profibus and DTM capabilities for troubleshooting are extensively dis-
cussed in SECTION 6 Operation.