Configurator Error and Warning Messages
D-2
Error Messages - Configuration
The table below lists the Error messages which can be displayed by the PROFIBUS Master Unit DTM in case
there are configuration errors. Usually, these are detected either when entering, or up on download. The table
suggests corrections to the problems in the right most column.
Number
Message
00
Total I/O area size exceeds maxi-
mum
01
PLC Memory overlapping
02
PLC Memory exceeds memory
range
03
Slaves should have unique
addresses
04
DTM cannot be added to the net-
work, it is not a PROFIBUS device
DTM
05
Max. number of slaves configured.
New slave cannot be added
06
Slave address overlap detected.
New address assigned: [new
address]
07
Invalid data set received from a
slave DTM. Slave parameter
changes ignored
08
Set Parameters failed. Slave can-
not be configured
09
No slaves assigned. Download
aborted
10
Slave(s) has no modules. Down-
load aborted
11
Configured EM bank (banks) is
not available in the connected
PLC.Download aborted
12
Connected unit is busy. Download
aborted
13
Slave configuration too big
14
Maximum number of modules
exceeded
Description
The I/O configuration exceeds the
maximum limit of 7168 (or 7k)
words).
Input/Output areas and/or PROFI-
BUS DP-V1 Status table are over-
lapping within the current
configuration.
Input/Output areas and/or PROFI-
BUS DP-V1 Status table exceeds
memory range (combination of start
address and length).
Unique bus addresses must be
assigned for each slave.
The slave DTM cannot be con-
nected, e.g. if adding HART device
DTM.
DTM can not be added, since the
master has already the maximum
number of slaves (125) assigned.
Changing the address of an existing
slave results in an address overlap.
An internal error has occurred pre-
venting the master DTM to obtain
the slave's parameter set.
An internal error has occurred pre-
venting the master DTM from set-
ting/changing the slave's bus
address.
No slaves have been assigned to the
master. At least one slave must be
assigned.
A slave (or slaves) has no modules.
The configured EM bank (banks) are
not available in the connected PLC.
Unit is busy with parameter storage. Retry download when parameter
The total number of configured
parameter bytes and configuration
bytes does not fit into the FINS mes-
sage for downloading.
The total number of configured I/O
modules over all allocated slave
devices can not exceed 4000.
Appendix D
Correction
Change configuration to reduce the
amount of I/O data to 7168 words
maximum or less.
Check the Input/Output areas and
make sure they are not overlapping.
Retry download.
Change the configuration to be
within the memory area and retry
download.
Change the addresses of the slaves
and ensure no duplicates are
present. Retry download.
Avoid using non-PROFIBUS DP
DTMs.
Do not add any more DTMs. If more
are still needed, a second PROFI-
BUS Master Unit on the same PLC
system may be solution.
Automatically recovers.
Add a new slave DTM into the net-
work (or change the modules of the
existing slave) with correct slave
parameter set.
Non recoverable. Master DTM tries
to assign a new bus address to the
slave DTM, but the slave DTM's
database is locked.
Retry download when at least one
slave has been assigned.
Retry download when modules have
been added to the slave(s) having
no modules.
Change the configuration to use only
memory areas available in the PLC
and retry download.
storage has finished.
Reduce the configuration.
Do not add any more modules to the
configuration.
249