Explicit Message Send (2801); Error Log Clear (0203) - Omron SYSMAC CS Series Operation Manual

Profibus master units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Command / Response Reference
5-2-6

ERROR LOG CLEAR (0203)

Command Format
Response Format
Response Codes
5-2-7

EXPLICIT MESSAGE SEND (2801)

Explanation
Note
Command Format
134
Clears the number of records stored in the PROFIBUS Master Unit error log.
21
03
Command
code
21
03
Command
Response
code
code
Response code
0000
Normal completion.
250F
Memory writing error. Error Log was not cleared normally.
260B
Cannot Clear the Error Log. The error cause still exists.
Sends an explicit message over the PROFIBUS network to an OMRON slave
device and receives a response.
The Explicit Message Send command sends a CIP-defined explicit message
to an OMRON PROFIBUS Slave device supporting CIP messages.
Unlike other FINS commands, the Explicit Message Send command specifies
the PROFIBUS Master Unit station address (i.e. the local node) as the CMND
instruction control code destination. The actual destination address, i.e.
address of the targeted slave device is specified using the Destination Station
Address in the Explicit Message Send command.
Always specify the PROFIBUS Master Unit address in the CMND instruction
control code. If another Unit's address is specified an error will occur.
1. For information on explicit messages for OMRON slave, refer to SmartSlice
GRT1-Series GRT1-PRT PROFIBUS Communication Unit Operation
Manual (W04E-EN-@).
2. Since station address 0 is reserved in FINS commands, the Master unit
and the targeted slave device must not have the station address set to 0.
3. The Explicit Message Send command is wrapped in a PROFIBUS DP-V1
Class 2 message. The handling of this message, i.e. establishing a con-
nection, transferring data and aborting a connection is done automatically
by the PROFIBUS Master unit.
28
01
Command
Class ID Instance ID
code
Service code
Destination
station address
Section 5-2
Description
996 bytes max.
Service data

Advertisement