PROFIBUS Master Unit
Item
Ambient temperatures
Ambient operating humidity
Vibration resistance
Shock resistance
Dielectric strength
Conformance to EMC and Electrical
safety standards
Settings
Indicators
PROFIBUS Connector
CIO Area words allocated for the CPU
Bus Unit
DM Area words allocated for the CPU
Bus Unit.
I/O Data allocations
PROFIBUS DP-V1 status flags
Reading slave device diagnostics
Reading and controlling the error log
Device state changes
Operating temperature: 0 to 55° C
Storage temperature: –20 to 75° C
10% to 90% (with no condensation)
Conforms to IEC60068-2-6, test Fc.
10 to 54.8Hz, 0.25-mm amplitude, 54.8 to 300Hz, acceleration:
2
29.4 m/s
in X, Y, and Z directions for 120 minutes each.
(Total time: 12 linear sweeps x 10 minutes / sweep = 120 minutes)
Conforms to IEC60068-2-27, test Ea.
2
196 m/s
three times each in X, Y, and Z directions
600 VAC (between isolated circuits)
EN61000-6-2: 2001
EN61000-6-4: 2001/CISPR11
EN61131-2:1994+a12:2000
Unit Number rotary switch, range: 0 ~ F (Hex)
7 LEDs, indicating Unit status and PROFIBUS status:
Unit status:
RUN (Green LED)
ERC (Red LED)
Host PLC status:
ERH (Red LED)
Configuration status:
PRM (Green LED)
PROFIBUS status:
BST (Green LED)
COMM (Green LED)
BF (Red LED)
9-pin sub-D female connector (#4/40 UNC thread)
Fixed allocation of 25 words per Unit.
CIO 1500 + (25 x Unit number)
CIO words provide:
• 2 words for software switches
• 1 word for the Global-Control
• 21 words for the Unit and Slave statuses
Fixed allocation of 100 words per Unit.
DM 30000 + (100 x Unit number)
DM Area allocated to the Unit is reserved for future use.
Maximum total size: 7168 words
I/O Data can be allocated to up to 2 input areas and 2 output areas.
Input and output areas can be mapped to CIO, DM, WR, and HR Areas,
as well as EM banks. Mapping must be defined through configurator.
DPV1 Connection/Abort status flags: 16 words.
The status flags can be mapped to CIO, DM, WR, and HR Areas, as
well as EM banks. Mapping must be defined through configurator.
The MEMORY AREA READ (0101) FINS command can be used to
obtain the last received Slave Diagnostics message.
Catalogues the history of error events. The Unit supports the following
Error Log related FINS commands:
• ERROR LOG READ
• ERROR LOG CLEAR
Allocated slave devices can be disabled and enabled in order to tempo-
rarily remove them from data exchange services. The Unit supports the
following FINS commands to implement this:
• RUN
• STOP
Specification
Section 1-3