Configurator Error and Warning Messages
Number
Message
51
Communication Failure with PLC
52
CX-Server could not be config-
ured
53
CX-Server could not be initialized
D-4
Error Messages - System
The table below lists the Error messages related to the System on which the DTM is installed.
Number
Message
100
Connected device can not be con-
figured with this DTM
101
Incorrect version of CX-Server.
Description
The communication between the PC
and the PLC could not be achieved.
Configuration of CX-Server failed.
Initialization of CX-Server was not
possible.
Description
Incorrect firmware type.
Incorrect version of CX-Server.
Appendix D
Correction
• Ensure there are no problems
with the connection between the
Personal Computer and the PLC.
• Make sure the Device Settings
are correct.
• When problem has been
removed, disconnect and re-con-
nect. Perform one of the following
successfully to confirm the prob-
lem has been solved:
* Update monitoring data (Slave
Diagnostics, clearing error log).
* Changing the master state
• Make sure the settings within the
Device Set-up tab are correct.
Select the Test Button to check
this.
• Make sure the Personal Com-
puter COM port selected within
the Device Set-up Configuration
is not in use by another applica-
tion. If it is close the connection
from within the other application.
• Restart CX-Profibus.
• Restart Personal Computer to
ensure COM port is released.
• Ensure the correct version of CX-
Server is installed on the Personal
Computer. Refer to the Master
Manual for installation details.
When the problem has been
removed, perform one of the fol-
lowing successfully to confirm the
problem has been solved:
* Select the Configure Button in
the Device Set-up tab
* Select the Test Button in the
Device Set-up tab
• Ensure the correct version of CX-
Server is installed on the Personal
Computer. Refer to the Master
Manual for installation details.
Correction
Make sure the unit connected is a
CS1W-PRM21 or CJ1W-PRM21.
Make sure the Unit number in the
Device set-up corresponds to the
physical unit.
Make sure the correct CX-Server
version is installed. Version must be
1.7 and up.
251