Outputs; Output Specifications - Prolon C1000 Series Hardware Manual

Rooftop controller
Hide thumbs Also See for C1000 Series:
Table of Contents

Advertisement

www.proloncontrols.com
The C1000 Basic Rooftop controller contains 5 customizable outputs, 4 being Triac type switch outputs
and one being 0-10Vdc analog modulating / pulsed / On-or-Off output. Some outputs are configurable
and follow a proportional and integral algorithm (PI) to ensure precise adjustment of the device. All
configurations are performed via the ProLon Focus software.
An integrated resettable fuse protects each of the outputs of the C1000 against current surges and short
circuits. This protection will cut the current to the output as soon as an overload condition is detected.
The fuse is a round, yellow-coloured PTC that will change to orange and heat up on an overload
condition. Once power has been removed from the C1000, the fuse will cool down and automatically
reset. Fix the faulty wiring and you will be able to activate the output once again.
Output
Triac source 24VAC
1
Max Current: 300 mA
Triac source 24VAC
2
Max Current: 300 mA
Triac source 24VAC
3
Max Current: 300 mA
Triac source 24VAC
4
Max Current: 300 mA
Configurable Analog
Output:
- 0 to 10 VDC
5
- 2 to 10 VDC
- 0 to 5 VDC
Max Current: 40 mA
info@proloncontrols.com
www.proloncontrols.com
BASIC ROOFTOP HARDWARE GUIDE

OUTPUTS

Output Specifications

Type
Action
On-or-Off
On-or-Off
On-or-Off
On-or-Off
Modulating
proportional
OR
Pulsed
OR
On-or-Off
1-877-9PROLON
PL-C1000 SERIES
Application
Fan
Cooling (1st Stage)
Cooling (2nd Stage)
Heating (1st or 2nd stage)
OR
Preheat permission
Preheating only
OR
Preheat + Heating
OR
Heating (1st or 2nd stage)
12
Montréal
1989 rue Michelin Laval,
QC H7L 5B7
TEL:(450) 973-5100
FAX: (450) 973-6186