Outputs; Output Specifications - Prolon C1050 Series Hardware Manual

Heatpump controller
Hide thumbs Also See for C1050 Series:
Table of Contents

Advertisement

Outputs

The C1050 Heatpump controller contains 5 customizable outputs, 4 being Triac type switch outputs and one being
0-10Vdc analog modulating / pulsed / On-or-Off output. Some outputs are configurable and follow a proportional and
integral algorithm (PI) to ensure precise adjustment of the device. Output configuration is performed via the Prolon
Focus software.
An integrated resettable fuse protects each of the four Triac outputs of the C1050 against current surges and short cir-
cuits. This protection will cut the current to the output as soon as an overload condition is detected. It consists of a round
yellow-coloured thermal fuse that will change to orange and heat up on a short circuit condition. When the faulty wiring
or circuit is fixed, the breaker will automatically reset and activate the output again.

Output Specifications

Output
Triac Source: 24VAC
1
Max Current: 300 mA
Triac Source: 24VAC
2
Max Current: 300 mA
Triac Source: 24VAC
3
Max Current: 300 mA
Triac Source: 24VAC
4
Max Current: 300 mA
Configurable Analog Output:
- 0 to 10 VDC
5
- 2 to 10 VDC
- 0 to 5 VDC
Max Current: 40mA
REV. 7.3.0 / PL-HRDW-HP-C1050-C/F-EN
Type
Action
On-or-Off
On-or-Off
On-or-Off
On-or-Off
Modulating
Proportional /
Pulsed /
On-or-Off
Applications
Application
(1 Compressor)
(2 Compressors)
Fan
Fan
Compressor
Compressor
(1st Stage)
Compressor
Reversing Valve
(2nd Stage)
Auxiliary Heat
Reversing Valve
Preheating /
Auxiliary Heat
Auxiliary Heat
(2nd Stage )/
Economizer
12