Input And Output Identification - Prolon C1000 Series Hardware Manual

Rooftop controller
Hide thumbs Also See for C1000 Series:
Table of Contents

Advertisement

www.proloncontrols.com

Input and Output Identification

All the inputs and outputs of the C1000 use pluggable screw type terminal blocks with elevator style
clamping, which make connections easier and more secure.
For incoming communication from a remote computer or network controller, an RJ45 type connector is
available. The RJ45 connector allows the use of premade CAT5 cables for simple plug-and-play RS485
communication. This RJ45 connector follows the Modbus pinout specification for RS485 communication.
RESET
RJ45 Pinout
1 2 3 4 5 6 7 8
B
A
GND
(-)
(+)
info@proloncontrols.com
www.proloncontrols.com
BASIC ROOFTOP HARDWARE GUIDE
A
NET
B
OCC
SUPPLY
GND
SETPT
ROOM
+
COM
24VAC
COM
24VAC
COM
24VAC
COM
24VAC
COM
1-877-9PROLON
PL-C1000 SERIES
INT Port: Incoming RS485 Network communication
(Modbus)
NET Port: Outgoing RS485 Network communication to
Zones (Modbus)
External dry contact for night setback
Supply air temperature sensor (10K thermistor)
Common for all inputs
Return air temperature sensor (10K thermistor)
Outside air temperature sensor (10K thermistor)
Output 5 (Analog 0-10VDC)
Preheating / Heat (W2)
Output 4 Heat (W1)
Output 3 Cooling (Y2)
Output 3 Cooling (Y1)
Output 1 Fan (G)
Controller's power source
Unit's R&C terminals (24VAC)