Outputs

The M2000 Boiler controller contains 8 customizable outputs; five triac ON/OFF outputs (24VAC) and three analog
outputs (0-10VDC). Output configuration is performed via the Prolon Focus software.
An integrated resettable fuse protects each of the outputs of the M2000 against current surges and short circuits. This
protection will cut the current to the output as soon as an overload condition is detected. The fuse is a round, yellow-co-
loured PTC that will change to orange and heat up on an overload condition. Once power has been removed from the
M2000, the fuse will cool down and automatically reset. Fix the faulty wiring and you will be able to activate the output
once again.

Output Specifications

Output
Triac source 24VAC,
DO 1
Max Current: 300 mA
Triac source 24VAC,
DO 2
Max Current: 300 mA
Triac source 24VAC,
DO 3
Max Current: 300 mA
Triac source 24VAC,
DO 4
Max Current: 300 mA
Triac source 24VAC,
DO 5
Max Current: 300 mA
Configurable Analog Output:
AO 1
- 0 to 10 VDC
Max Current: 40 mA
Configurable Analog Output:
- 0 to 10 VDC
AO 2
- 2 to 10 VDC
- 0 to 5 VDC
Max Current: 40 mA
Configurable Analog Output:
- 0 to 10 VDC
AO 3
- 2 to 10 VDC
- 0 to 5 VDC
Max Current: 40 mA
REV. 7.2.0 / PL-HRDW-BLR-M2000-C/F-EN
Type
On-or-Off
On-or-Off
On-or-Off
On-or-Off
On-or-Off
On-or-Off
Modulating Proportional
Modulating Proportional
Action
Application
Boiler Stage 1
Boiler Stage 2
Boiler Stage 3
Boiler Stage 4
Pump 1
Pump 2
Modulating Boiler
Three way valve /
Modulating Boiler
(Backup)