Occupancy Mode (Night Setback); Dry Contact Originating From An External Timer - Prolon C1000 Series Hardware Manual

Rooftop controller
Hide thumbs Also See for C1000 Series:
Table of Contents

Advertisement

www.proloncontrols.com

Occupancy Mode (Night Setback)

Dry Contact originating from an External Timer:

Temperature setback savings can be obtained by using a dry contact originating from an external timer
to switch the controller from occupied to unoccupied mode. The timer contact used must be connected
to the "OCC" and the "GND" terminals (see Figure 3). To indicate occupied mode, the contact must be
open. To indicate unoccupied mode, the contact must be closed. As a network Master, the Rooftop
controller will then send the occupancy status to all known slaves on his network.
A
NET
B
OCC
SUPPLY
GND
RA
OA
info@proloncontrols.com
www.proloncontrols.com
BASIC ROOFTOP HARDWARE GUIDE
Figure 3: Night setback contact connection
1-877-9PROLON
PL-C1000 SERIES
Timer
11
Montréal
1989 rue Michelin Laval,
QC H7L 5B7
TEL:(450) 973-5100
FAX: (450) 973-6186

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pl-c1000 series

Table of Contents