Resetting or restoring settings

Fig.92
Configuration numbers
A
98
AMC
Description
HPFlowOverTMax
SourcePumpPostRun
HumiditySensorStopHP
WaterFlowStopHP
HumidityInt.Setpoint
HP&BackupRelieved
HPRelievedForCooling
OutsideTempStopHP
HeatPumpOffOverLimit
DeAirPumpOn&ValveCH
DeAirPumpOn&ValveDhw
DeAirPumpOff&ValveCH
DeAirPumpOff&ValvDhw
BLInputBackupLimited
HPLimited
Backup&HPLimited
BLInputLowTariff
PV-WithHP
PV-WithHP&Bckp
BLInputSmartGrid
WaitingForWaterpress
NoProducerAvailable
FreeCoolingPumpOff
FreeCoolingPumpON
SourcePumpPreRunning
Calibration
Initialising Done
Initialising Csu
Init. Identifiers
Init.BL.Parameter
Init. Safety Unit
Init. Blocking
StateUnknown
SuOutOfResetsWait1Hr
B
C
AD-3000935-01
9.7.1

Resetting the configuration numbers CN1 and CN2

The configuration numbers must be reset when indicated by an error
message or when the control unit has been replaced. The configuration
numbers can be found on the data plate of the appliance.
A Select the control unit
B Extra information
C Configuration numbers
1. Press the
button.
2. Select Advanced Service Menu > Set Configuration Numbers.
3. Select the control unit you want to reset.
4. Select and change the CN1 setting.
5. Select and change the CN2 setting.
6. Select Confirm to confirm the changed numbers.