Factory Configuration Of Circuits; Boiler Settings With Scb-10 Control - DeDietrich AMC 15 Installation And Service Manual

Wall-hung gas condensing boilers
Table of Contents

Advertisement

Tab.27
Installation Setup > CU-GH08 > CIRCA > Parameters, counters, signals > Parameters
Code
Display text
CP020
Zone Function
Tab.28
Installation Setup > CU-GH08 > Gas fired appliance > Parameters, counters, signals > Parameters
Code
Display text
AP102
Boiler Pump function
Tab.29
Installation Setup > CU-GH08 > Tank DHW > Parameters, counters, signals > Parameters
Code
Display text
DP007
Dhw 3wv Standby
7686707 - v.01 - 06092018
Symbol
6.7.2

Factory configuration of circuits

From the factory, the different circuits are configured as shown in the
table. You can modify this configuration and adapt it to the needs of your
installation.
Tab.26
Factory circuit configuration
Circuit
CIRCA
CIRCB
CIRCC
6.7.3

Boiler settings with SCB-10 control

When the boiler is fitted with the SCB-10 control board the following boiler
parameter(s) at installer level must be checked and adjusted, if necessary:
Description
Functionality of the zone
Description
Configuration of the boiler pump as
zone pump or system pump (feed
lowloss header)
Description
Position of three way valve during
standby
For the hydraulic connections as shown, where some parameters must be
adjusted, the parameter settings are arranged in three levels:
1. End user level
Explanation
Hot-air heater
Swimming pool
Circuit type
Direct heating circuit
Circuit with 3 way valve
Circuit with 3 way valve
Range
0 = Disable
1 = Direct
2 = Mixing Circuit
3 = Swimming pool
4 = High Temperature
5 = Fan Convector
6 = DHW tank
7 = Electrical DHW
8 = Time Program
9 = ProcessHeat
10 = DHW Layered
11 = DHW Internal tank
31 = DHW FWS EXT
Range
0 = No
1 = Yes
Range
0 = CH position
1 = DHW position
6 Installation
Adjust­
ment
0
Adjust­
ment
0
Adjust­
ment
0
AMC
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amc 25/28 miAmc 25Amc 35

Table of Contents