Olimpia BS-1638 Installation, Programming, Use page 46

Conventional fire detection panels 8, 12 and 16 zones
Table of Contents

Advertisement

Autonomy
Degrees of cover
protection
Cables
Fuse type
Operating temperature
range
Humidity
Construction material
Dimensions (LxWxH)
Weight(without batteries)
Produced in accordance
with
Guarantee
Optional panel functions
Design
72 hours (Maximum number of connected detectors 220 and 16 zones, no
loads connected to the 24V M and 24VP outputs) with two 12V/7Ah
Cables suitable for fire detection systems such as FIP200, MICC,
The panel has only one fuse that is replaceable and which protects the
main power supply connection. This fuse has a rating of F 4A 250V TR5
and must be replaced with a fuse of the same type and rating.
ABS – polycarbonate, electrostatically painted steel
3740gr
The optional functions of the panel according to the norm ΕΝ 54-2 are
(Fire alarm device(s)) paragraph 7.8 ( ΕΝ 54-2 )
(Test condition) paragraph 10 ( ΕΝ 54-2 )
(Alarm counter) paragraph 7.13 ( ΕΝ 54-2 )
(Delays to outputs) paragraph7.11 ( ΕΝ 54-2 )
Components of the panels have been selected for the intended purpose,
and are expected to operate within their specification when the
environmental conditions outside the cabinet of the panel comply with
class 3k5 of EN 60721-3-3:1995.
46 / 47
batteries.
IP 30
PYROFIL
0 to 50 °C
Up to 95% relative humidity
345 x 106 x 348 mm
3780gr
ΕΝ 54-2, ΕΝ 54-4
2 years
Date
30/9/2016
File
Document code
921163800_09_007
Page
46 from 47
3820gr