Figure 5-3 shows the tree detail of this menu.
Next there will be a detailed description of each option.

Test menu

5.1
In this option we can adjust the state of each zone during the test. The setting is done using the option
«ZONES IN TEST» where we can select which zone will be on test.
After adjusting this we can test the zones without affecting the outputs of the panel. The state of the
zones in test can be found in the option INFORMATIONZONES ZONES IN TEST, ALARMS IN
TEST ZONES and FAULTS IN TEST ZONES.
To reset the zones to normal operation use the option «UNSET ZONE IN TEST».
TECHNICIAN
TEST
CONFIGURATION
SETTINGS
CLEAR EVENTS
RESET COUNTER
NETWORK
Figure 5-32. Technician menu
ZONES IN TEST
SET ZONES IN TEST
RESET ZONES IN TEST
NUMBER OF ZONES
AUXILIARY RELAYS
SELECT LANGUAGE
ANNUAL TEST
FACTORY DEFAULTS
ANNUAL TEST OK
CHANGE TECH CODE
MANUFACTURER MENU
ETHERNET CARD
RESET ETHERNET