4.10 Other Connections

The following paragraphs mention all the connections that can be achieved with the panel.
Every connection must use a separate cable (e.i. a triple cable for connecting the panel to the
230VAC mains power supply, a double cable for the sirens e.t.c.).
The shield of each cable must be connected to the main ground terminals of the panel
The zone and input-output PCB contains the following outputs:
-
24V_M: A 24V dc output (up to 300mΑ) that is interrupted during a reset of the panel. It is used to
power gas detectors or other devices that need the power interrupted during a panel reset.
-
24V_P: A 24V dc output (up to 300mΑ) that is not interrupted during a panel reset. It can be
used to power electromagnetic door latches.
Relay Alarm : Voltage free relays contacts that are activated during an alarm.
-
Relay Fault : Voltage free relays contacts that are activated during a fault.
-
-
Relay AUX : Voltage free relays contacts that are programmable from the panel.
-
WARNING: The maximum rating of the relays is 30VDC and 3A.
Relay per Zone : The panel has outputs to connect up to 4 BS-613 (4 zone expansion card with
-
relays). For example, if we want the relay of zone 3 we must connect a BS-613 to the connector
Flat cable 1. The photo below shows which relay belongs to which zone.