Technical Characteristics - Specifications - Olimpia BS-1638 Installation, Programming, Use

Conventional fire detection panels 8, 12 and 16 zones
Table of Contents

Advertisement

6 Technical Characteristics - Specifications

Description
Mains power supply
Consumption
Battery type
Charger
Zone circuits
Alarm circuits
Output 24P
Output 24M
Output relays
Total power
Battery cut of voltage
Maximum current
batteries discharge
Battery maximum
internal resistance
Rimax
BS-1638
Fire Detection panel
with 8 zones
2 sealed lead acid batteries 12V / 7Ah
Stabilized power supply 27,6V / 350mA
8 circuits that
monitored for open and
short-circuit conditions
(maximum current
35mA)
Two 24V circuits that are monitored for open and short-circuit conditions
(The maximum current for each circuit is 300mA). Each output is protected
by a self resetting electronic fuse.
24VDC ( ±3VDC) permanent output with a maximum current of 0.3A.
μόνιμη έξοδος με μέγιστο ρεύμα εξόδου 0.3 A The output is protected by a
24VDC ( ±3VDC) output which is interrupted during a reset. The output
has a maximum current output of 0.3 A
The output is protected by a self resetting electronic fuse.
Three relay contacts that can handle up to 30V DC and 5A maximum.
Do not exceed these limits in any case.
All the output relays must be protected with fuses with the same rating.
The total output power (zone circuits, siren circuits,
outputs 24P and 24M) must not exceed 1A.
Imax a=Imax b=1A, Imin=60mA
45 / 47
Document code
BS-1642
Fire Detection panel
with 12 zones
220-240V AC/50-60HZ
100 VA
12 circuits that
monitored for open and
short-circuit conditions
(maximum current
35mA)
resetable electronic fuse.
21V
1A
1Ohm
Date
30/9/2016
File
921163800_09_007
Page
45 from 47
BS-1646
Fire Detection panel
with 16 zones
16 circuits that
monitored for open
and short-circuit
conditions (maximum
current 35mA)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bs-1642Bs-1646Bs-1638/marBs-1642/marBs-1646/mar

Table of Contents