Connecting The Batteries - Olimpia BS-1638 Installation, Programming, Use

Conventional fire detection panels 8, 12 and 16 zones
Table of Contents

Advertisement

9. The battery fuse is 900mA and is self resetting.

Connecting the batteries.

4.6
The panel has space with suitable dimensions for installing batteries of the type Α-986 from olympia
electronics. The charging circuit has been adjusted for these specific batteries. Should the batteries need
replacing, replace them with the same type and rating.
The batteries should be connected in series. The battery compartment contain two cables, one red and
one black, which are connected to the panel and one more cable that is not connected. These cables
must be connected in a specific order. The red cable must be connected to the positive contact (+ RED)
of the first battery. The black cable should be connected to the negative contact (- BLACK) of the second
battery. The third cable is used to connect the negative contact (- BLACK) of the first battery to the
positive contact (+ RED) of the second battery.
This connection is shown in the diagram below.
The batteries used should be 2x Α-986 12V (7Ah) lead acid type with a voltage of 12V. There
capacity must be 7Ah or 9Αh (Α-961).
Battery Recycling. It is not allowed to dispose batteries in common waste bins. They should be
disposed only in special battery recycling collection points.
+
Battery (1)
+
Figure 4-23. Connecting the batteries in series.
29 / 47
Document code
2
x
12
V Battery - connection diagram
+
Battery (2)
Date
30/9/2016
File
921163800_09_007
Page
29 from 47