Specifications - Unitronics Unistream URD-0800 User Manual

Remote i/o
Table of Contents

Advertisement

Specifications

Max. Expansion Module
Max Length Bus Line
Max. Nodes
Baud Rate
Interface Connector
IP-Address Setup
IP-Address Range
Indicator
System Power
Power Dissipation
Current for I/O Module
Isolation
Field Power
Max. Current Field Power Contact
Weight
Module Size
Unitronics
Items
Up to 63 slots
The adapter is limited to process 192 data bytes for inputs and 192 data bytes for
outputs.
Each digital input/output point process data is 1 bit (minimum 1 byte per module if
module data size is less than 8 points) while each analog input/output is 2 bytes
(8 inputs/outputs module will be 16 bytes of process data).
Up to 100m from Ethernet Hub/Switch with twisted CAT5 UTP/STP
Limited by Ethernet Specification.
10/100Mbps, Auto-negotiation, Full duplex
2 ports, RJ-45 socket
DIP Switch or DHCP/BOOTP
xxx.xxx.xxx.1 ~ 253 (User area)
xxx.xxx.xxx.254 ~ 255 (Reserved for IAP Function)
6 LEDs
1 Green/Red, Module Status (MOD)
1 Green, Physical Connection (LINK)
1 Green, Exchange Data/Traffic Present (ACTIVE)
1 Green/Red, Expansion I/O Module Statsus (IOS)
1 Green, System Power Status
1 Green, Field Power Status
2 LEDs (each RJ45 Connector)
1 Yellow, Link/Active
1 Green, Not used
For detailed indicators description, please follow the
bellow.
Supply voltage : 24VDC nominal
Supply voltage range : 15~32Vdc
Protection :
Output current limit (Min. 1.5A)
Reverse polarity protection
70mA typical @ 24VDC
1.5A @ 5VDC
System power to internal logic : Non-isolation
System power I/O driver : Isolation
Supply voltage : 24VDC typical (Max. 32VDC)
Field Power Range is different depending on URI module series.
Refer to URI module`s specification.
DC 10A Max
162g
54mm x 99mm x 70mm
Specification