URA-0004Z (AO04Z) - 4 Analog Voltage Outputs 16bit

Outputs per module
Indicators(Logic side )
Resolution in Ranges
Output Range
Data Format
Module Error
Load Resistance
Conversion Time
Diagnostic
Calibration
Common Type
Power dissipation
Isolation
Field Power
Wiring
Weight
Module Size
Operating temperature
Unitronics
Items
Specification
4 Outputs single ended
4 Green Output status
16 bit (Include Sign)
15 bits : 0.31mV/bit
0 ~ 10VDC
16bits Integer (2' compliment)
±0.1% Full Scale @ 25°C (77°F) ambient
±0.3% Full Scale @ -40°C to 70°C (-40°F to 158°F)
Min. 2KΩ
Max. 150usec / All output
Field Power Off: LED Blinking
Field Power On: No Output LED Off
Field Power On: Output LED On
Not Required
4 Common, Field Power 0V is Common(AGND)
Max. 30mA @ 5.0Vdc
I/O to Logic : Isolation
Field power : Non-Isolation
Supply Voltage : 24Vdc nominal
Voltage Range : 18 to 32VDC
Power Dissipation : Max. 35mA @ 24VDC
2
I/O Cable Max. 2.0����
(AWG 14)
58g
12mm x 99mm x 70mm
-40°C to 70°C (-40°F to 158°F)