URS-08RT-2 (S08RT2) - 8 RTD / Resistance

Inputs per module
Indicators(Logic side )
Sensor Types
Excitation Current
Connection Method
Conversion Time
Data Format
Module Accuracy
Resolution of Data
Calibration
Diagnostic
Power dissipation
Isolation
Field Power
Wiring
Weight
Module Size
Operating temperature
Unitronics
Items
Specification
8 Channels
8 Green Input status
RTD Input Range
RTD Input
PT100, PT200, PT500, PT50
PT1000
JPT100, JPT200, JPT500, JPT50
JPT1000
NI100, NI200, NI500
NI1000
NI120
NI1000LG
Resistance Input
100mΩ/bit
10mΩ/bit
20mΩ/bit
50mΩ/bit
About 1mA
3-Wire
< 280ms, All Channel
16bits signed Integer (2' complement )
PT100, PT1000 type Range
±0.5°C(32.9°F) @ 25°C (77°F)
All type Input Range
±0.1% Full Scale @ 25°C (77°F) ambient
±0.3% Full Scale @ 40°C to 70°C (-40°F to 158°F)
RTD Type : ±0.1°C / F , Resitance Type : 100mΩ, 10mΩ, 20mΩ, 50mΩ
Not Required
Sensor open or range over, then conversion data = 0x8000(-32768)
Max. 120mA @ 5.0VDC
I/O to Logic : Isolation
Field power : Not Connected
Not used, Field power bypass to next expansion module
2
I/O Cable Max. 2.0����
(AWG 14)
60g
12mm x 99mm x 70mm
40°C to 70°C (-40°F to 158°F)
Input Range
-200~850°c (-328°F, 1562°F)
-200~350°c (-328°F, 662°F)
-200~640°c (-328°F, 1184°F)
-200~350°c (-328°F, 662°F)
-60~250°c (-76°F, 418°F)
-60~180°c (-76°F, 356°F)
-80~260°c (-112°F, 500°F)
-50~120°c (-58°F, 248°F)
Input Range
0~2000Ω
0~327Ω
0~620Ω
0~1200Ω
137