Remote Mount Feedback Unit
The DVC6005 base unit is designed to receive travel information via a DVC6015, DVC6025 or DVC6035 feedback unit.
WARNING
Personal injury or property damage, caused by wiring failure, can result if the feedback wiring connecting the base unit
with the remote feedback unit shares a conduit with any other power or signal wiring.
Do not place feedback wiring in the same conduit as other power or signal wiring.
Note
3‐conductor shielded cable, 22 AWG minimum wire size, is required for connection between base unit and feedback unit.
Pneumatic tubing between base unit output connection and actuator has been tested to 91 meters (300 feet). At 15 meters
(50 feet) there was no performance degradation. At 91 meters there was minimal pneumatic lag.
1. Remove the termination caps from both the feedback unit and the DVC6005 base unit.
2. Install conduit between the feedback unit and the base unit following applicable local and national electrical codes.
Route the 3‐conductor shielded cable between the two units (refer to figure 23).
Figure 23. Terminal Details for Connecting Base Unit and Feedback Units of Remote‐Mounted Digital Valve
Controllers
FEEDBACK
CONNECTIONS
TERMINAL BOX
GROUND
SCREW
W8476
FEEDBACK CONNECTIONS TERMINAL BOX
W8475
BASE UNIT
TO FEEDBACK UNIT
TERMINAL 3
TO FEEDBACK UNIT
TERMINAL 2
TO FEEDBACK UNIT
TERMINAL 1
DVC6005 Digital Valve Controllers
W8477
FEEDBACK UNIT
TERMINAL 1
TERMINAL 2
TERMINAL 3
W8478‐1