DVC6005 Digital Valve Controllers
March 2018
Smart Wireless THUM Adapter
Refer to the Smart Wireless THUM Adapter quick installation guide (00825­0100­4075) for additional information.
Note
The recommended mounting orientation for the THUM Adapter is vertically up, for optimal wireless communication range.
However, when mounting on the DVC6005 HW2, it may be mounted horizontally, as shown in figure 19. Note that mounting
horizontally may result in a decreased communication range.
Figure 19. THUM Adapter Installed On DVC6005 HW2 Digital Valve Controller
X0796-1
1. Remove the DVC6005 terminal box plug from the top conduit entrance.
2. Thread the THUM Adapter into the top conduit entrance.
3. Using the wire splice included with the THUM Adapter (or other suitable wire splice), connect the wires as shown in
figure 20 below.
Figure 20. Wiring the THUM Adapter
4-20 mA
LOOP +
4-20 mA
LOOP -
SPLICE
CONNECTOR
GG18677
4. Carefully coil the wires inside the terminal box.
5. Replace and hand tighten the cover on the terminal box.
6. Proceed to page 27 for remote mount feedback unit wiring.
24
TOP CONDUIT ENTRANCE
WIRED DEVICE
GROUND
LOOP -
LOOP +
THUM ADAPTER
GREEN
RED
BLACK
WHITE
YELLOW