Download Print this page
Emerson Fisher EZR Relief Installation Manual
Emerson Fisher EZR Relief Installation Manual

Emerson Fisher EZR Relief Installation Manual

Advertisement

Quick Links

Installation Guide
D102629X014
English – October 2015
Introduction
This installation guide provides instructions for installation,
startup and adjustment. To receive a copy of the
instruction manual, contact your local Sales Office or view
a copy at www.fisher.com. For further information refer to:
Type EZR Relief Instruction Manual, D102629X012.
P.E.D. Categories
This product may be used as a pressure accessory with
pressure equipment in the following Pressure Equipment
Directive categories. It may also be used outside of the
Pressure Equipment Directive using sound engineering
practice (SEP) per table below. For information on the
current PED revision see Bulletin: D103053X012.
PRODUCT SIZE
DN 25, 50, 80, 100 and 150 /
NPS 1, 2, 3, 4 and 6
Specifications
Main Valve Body Size, End Connection Styles
and Body Ratings
(1)
See Table 1
Maximum Relief (Inlet) Pressure
See Tables 2 and 5
Minimum Relief Set Pressure
1.4 bar / 20 psig
Set Pressure Control Ranges
See Table 2
Temperature Capabilities
See Table 4
Installation
!
Only qualified personnel should install
or service a backpressure regulator.
Backpressure regulator should be
installed, operated and maintained
in accordance with international and
applicable codes and regulations
and Emerson Process Management
Regulator Technologies,
Inc. instructions.
1. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded.
CATEGORIES
FLUID GROUP
III
(1)
(1)
(1)
WARNING
If using a backpressure regulator on a
hazardous or flammable fluid service,
personal injury and property damage
could occur due to fire or explosion of
vented fluid that may have accumulated.
To prevent such injury or damage,
provide piping or tubing to vent the
fluid to a safe, well-ventilated area or
containment vessel. Also, when venting
a hazardous fluid, the piping or tubing
should be located far enough away
from any buildings or windows so to
not create a further hazard, and the vent
opening should be protected against
anything that could clog it.
Personal injury, equipment damage
or leakage due to escaping fluid or
bursting of pressure-containing parts
may result if this backpressure regulator
1
is overpressured or is installed where
service conditions could exceed the limits
given in the Specifications section, or
where conditions exceed any ratings of
the adjacent piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
code, regulation or standard) to prevent
service conditions from exceeding limits.
Additionally, physical damage to the
backpressure regulator could result in
personal injury and property damage due
to escaping fluid. To avoid such injury and
damage, install the backpressure regulator
in a safe location.
Clean out all pipelines before installation of the
backpressure regulator and check to be sure the
backpressure regulator has not been damaged or has
collected foreign material during shipping. For NPT
bodies, apply pipe compound to the external pipe
threads. For flanged bodies, use suitable line gaskets
and approved piping and bolting practices. Install the
backpressure regulator in any position desired, unless
otherwise specified, but be sure flow through the body
is in the direction indicated by the arrow on the body.
Type EZR Relief

Advertisement

loading

Summary of Contents for Emerson Fisher EZR Relief

  • Page 1 Emerson Process Management Regulator Technologies, Inc. instructions. 1. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded.
  • Page 2: Overpressure Protection

    Type EZR Relief Table 1. Main Valve Body Sizes, End Connection Styles and Structural Design Ratings MAIN VALVE BODY SIZE STRUCTURAL DESIGN RATING MAIN VALVE BODY MATERIAL END CONNECTION STYLE psig NPT (NPS 2 / DN 50 only) 27.6 50, 80, 100 2, 3, 4 and 6 Cast Iron CL125 FF...
  • Page 3 Type EZR Relief Table 3. Main Valve Minimum Differential Pressures MINIMUM DIFFERENTIAL, PERCENT OF CAGE CAPACITY MAIN VALVE MAIN SPRING PART FOR 90% CAPACITY FOR 100% CAPACITY DIAPHRAGM BODY SIZE NUMBER AND MATERIAL 100% Trim 60% Trim 30% Trim 100% Trim 60% Trim 30% Trim COLOR CODE...
  • Page 4 Type EZR Relief Table 5. Main Valve Maximum Pressure Ratings MAXIMUM MAXIMUM MAXIMUM EMERGENCY OPERATING BODY SIZE OPERATING INLET INLET AND DIAPHRAGM MAIN SPRING DIAPHRAGM DIFFERENTIAL PRESSURE DIFFERENTIAL MATERIAL COLOR CODE DESIGNATION PRESSURE PRESSURE psig bar d psid bar d psid Light Blue 17E68 Nitrile (NBR)
  • Page 5 Type EZR Relief Parts List Type EZR Main Valve 6358 Series Pilots Description Description Pilot Body Valve Body Spring Case Bonnet Assembly Body Plug Cap Screw Valve Plug Hex Nut Diaphragm Assembly Top Plug Connector Cap O-ring Control Spring Cage Spring Seat Cage O-ring Stem Guide...
  • Page 6: Diaphragm Assembly

    Type EZR Relief TOP PLUG (KEY 5) O-RING (KEY 14) O-RING (KEY 70) DIAPHRAGM (KEY 9) BOTTOM PLUG (KEY 11) O-RING (KEY 10) 19B2408 LOCK WASHER (KEY 130) SOCKET HEAD SCREW (KEY 129) DN 25 / NPS 1 DIAPHRAGM ASSEMBLY B2617_2 MAIN VALVE ASSEMBLY FOR DN 25, 50, 80 AND 100 / NPS 1, 2, 3 AND 4 BODY SIZES Figure 1.
  • Page 7 Type EZR Relief 48B2142_C DN 25, 50, 80 AND 100 / NPS 1, 2, 3 AND 4 BODY SIZES DN 150 / NPS 6 BODY SIZE Figure 2. Type EZR Travel Indicator Plug Option A6920 6358 SERIES PILOT INTERIOR VIEW B2620-2 TYPE 6358EB PILOT INTERIOR VIEW A6920-2...
  • Page 8 Technologies, Inc. All rights reserved. 06/18. McKinney, Texas 75070 USA Singapore 128461, Singapore The Emerson logo is a trademark and service mark of Emerson T +1 800 558 5853 T +65 6777 8211 Electric Co. All other marks are the property of their prospective owners.