DVC6005 Digital Valve Controllers
March 2018
WARNING
Personal injury or property damage, caused by fire or explosion, can result from the discharge of static electricity. Connect
2
a 14 AWG (2.08 mm
) ground strap between the digital valve controller and earth ground when flammable or hazardous
gases are present. Refer to national and local codes and standards for grounding requirements.
4. Make connections to the ground terminal(s) following national and local codes and plant standards. As shown in
figure 21, two ground terminals are available for connecting a safety ground, earth ground, or drain wire. The safety
ground terminal is electrically identical to the earth ground.
5. Replace and hand tighten the cover on the terminal box.
6. Write the valve tag number on the top and bottom of the paper commissioning tag, as shown in figure 22.
Figure 22. Paper Commissioning Tag
18B9406-G
7. Remove the lower half of the paper commissioning tag and deliver it to the control system configurator. With the
piece of paper, the control system configurator will be able to easily change the Device ID placeholder to the actual
valve tag number.
Note
Alternatively, the valve tag number can be entered at the factory when specified at the time of order entry. When the valve tag
number is electronically stored in the DVC6005f, the control system will display the valve tag number instead of the Device ID. As a
result, step 6 and 7 will not be required.
8. Proceed to page 27 for remote mount feedback unit wiring.
26
WRITE THE VALVE
TAG NUMBER HERE
Quick Start Guide
D103784X012