Smb130: Freeport Control For Port 1 (See Smb30); Smb136-Smb145: Hsc3 High-Speed Counter; Smb186-Smb194: Receive Message Control (See Smb86-Smb94); Smb480-Smb515: Data Log Status - Siemens Simatic S7 Series System Manual

Hide thumbs Also See for Simatic S7 Series:
Table of Contents

Advertisement

D.19

SMB130: Freeport control for port 1 (See SMB30)

Refer to "SMB30: (port 0) and SMB130: (port 1)" (Page 674) for details.
D.20

SMB136-SMB145: HSC3 high-speed counter

Refer to "SMB36-45 (HSC0), SMB46-55 (HSC1), SMB56-65 (HSC2), SMB136-145 (HSC3):
high-speed counters" (Page 675) for details.
D.21

SMB186-SMB194: Receive message control (See SMB86-SMB94)

Refer to "SMB86-SMB94 and SMB186-SMB194" (Page 681) for details.
D.22

SMB480-SMB515: Data log status

SMB480 through SMB515 are read-only special memory addresses that are used to monitor
the status of Data log operations.
S7-200 SMART
symbol name
DL0_InitResult
DL1_InitResult
DL2_InitResult
DL3_InitResult
DL0_Maximum
DL0_Current
DL1_Maximum
DL1_Current
DL2_Maximum
DL2_Current
DL3_Maximum
DL3_Current
S7-200 SMART
System Manual, 09/2015, A5E03822230-AC
SM address
Function
SMB480
Initialization result code for Data Log 0: The data log analysis is per-
formed after power-up and after System block download.
SMB481
Initialization result code for Data Log 1 (See SMB 480 for result codes)
SMB482
Initialization result code for Data Log 2 (See SMB 480 for result codes)
SMB483
Initialization result code for Data Log 3 (See SMB 480 for result codes)
SMW500
Data log 0: Configured maximum allowed number of records
SMW502
Data log 0: Actual maximum allowed number of records
SMW504
Data log 1: Configured maximum allowed number of records
SMW506
Data log 1: Actual maximum allowed number of records
SMW508
Data log 2: Configured maximum allowed number of records
SMW510
Data log 2: Actual maximum allowed number of records
SMW512
Data log 3: Configured maximum allowed number of records
SMW514
Data log 3: Actual maximum allowed number of records
Special memory (SM) and system symbol names
D.19 SMB130: Freeport control for port 1 (See SMB30)
00H: data log OK
01H: initialization in progress
02H: data log file not found
03H: data log initialization error
04H to FEH: reserved
FFH: data log not configured
685

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-200 smart series

Table of Contents